您好,歡迎來到上海乾拓貿易有限公司!
Product center
產品型號:
所屬分類:TURCK傳感器
更新時間:2024-08-03
簡要描述:TURCK總線模塊,RI-10 S10C-2B2000-C-1M冗余供電可插拔螺釘式端子用于HSE現場總線診斷的RJ45接插件Inrush current limited to max. ~890 mA.Output voltage drops to 7 VDC then
TURCK總線模塊,RI-10 S10C-2B2000-C-1M
模塊機架可安裝Z多8個電源模塊和1個診斷模塊,以用于Z多4個H1網段
模塊機架可安裝Z多8個電源模塊和1個診斷模塊,以用于Z多4個H1網段
冗余供電可插拔螺釘式端子
用于HSE現場總線診斷的RJ45接插件
Inrush current limited to max. ~890 mA.
Output voltage drops to 7 VDC then
Retroactive effect on adjacent channel:
2 x 8-channel field barrier with 15 field
devices, IPS1 module with redundant
module on channel 4; channel 3 shortcircuited
resp. IPS1 module pulled/plugged.
increases again to 28.5 V. Duartion ofprocess ~4 ms.
15 field devices of different manufacturers were mounted to the field barriers, the last channel of the
second field barrier was left unassigned. The type of module rack used for the DPC-49
TURCK總線模塊,RI-10 S10C-2B2000-C-1M?
depends on the
type of connection to the DCS. The DPC-49-4RMB/SY was used with redundant connection, whereas the
DPC-49-4RMB was used with simple connection. The total current consumption of the segement was
~240 mA.limited by the IPS1 modules, controlled start-up of connected fieldbus segement. No measurable crosstalk
between the trunk outputs, single segment failures had no effect on the other segments. Replacing
the redundant IPS1 module has only minor physical effects, any influence on the communication was notmeasurable.
15 field devices were fully operated at the above mentioned control systems and the communication was
monitored for several days according to failure. The following cases of redundancy were additionally
tested at the redundantly connected system: Failure of controller I/O card, wire-break of H1 cable
between I/O card and DPC-49 rack and failure of IPS1module at DPC-49.
Result: No failures were observed, the DPC system worked properly on all control systems.
TURCK總線模塊,RI-10 S10C-2B2000-C-1M